Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM01813
Parcel: 136174110

Review Status: Active

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T20CM01813
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
03/26/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change The 1" gas pipe supply a total 249,000 BTU at a TDL of 67' is undersized, Table G2413.4(1). Change to 1-1/4" or show separate branch lines from the meter to each appliance.

Ken Van Karsen
837-4912

Final Status

Task End Date Reviewer's Name Type of Review Description
03/21/2020 ANY REJECT SHELF RECEIVED