Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T20CM01812
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/24/2020 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/06/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 04/16/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Ref; Equipment Layout Plan # 2019061. (a) Provide a legend that correlates with all the symbols and words along the conduit runs. (b) Where is inverter 'B' located? 2. Ref; 3 Line Diagram Plan #2019063B. (a) Provide a complete 3 line diagram in detail, including all associated equipment, all meters, service entrance conductors, etc. Provide more detail about the "SERVICE DISCONNECT and ENERGY SOURCE COMBINER". (b) What do the stars with numbers inside represent? 3. Provide a grounding detail for the racking and modules. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
| 04/17/2020 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 04/20/2020 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/04/2020 | ARAMIRE4 | REJECT SHELF | Completed |