Permit Number: T20CM01798
Parcel: 107040140

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM01798
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/22/2020 JVINCEN1 FIRE REVIEW Approved Once again. Provide sprinkler analysis. The information you provided is unrelated. We need sprinkler analysis based on IFC 2018 CH. 32 and NFPA 13 for storage (commodity classification, type of material, encapsulated or nonencapsulated, aisle spacing, temp rating of overhead sprinklers, type of racks, etc, etc..)
09/22/2020 JVINCEN1 FIRE REVIEW Approved Letter provided by owner and A-AAA fire states that the fire sprinklers will not need to be modified like adding a pump since the commodity is tile. Approving the work flow so that they can start the building. Any fire sprinkler work will require a permit to be obtained from TFD.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/18/2021 YLEON1 APPROVAL SHELF Completed
03/18/2021 YLEON1 OUT TO CUSTOMER Completed
03/18/2021 YLEON1 REJECT SHELF Completed