| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/01/2020 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | Please indicate how tall the racks will be, and what the top of storage on those racks will be. Storage above 12' AFF is considered "high-piled storage", and if you plan to store above 12', an analysis of the sprinkler system must be performed. |
| 04/23/2020 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Section Manager PROJECT: Dragoon Business Center T20CM01798 TRANSMITTAL DATE: April 23, 2020 1. Zoning has reviewed the building plans for compliance with the approved development package DP20-0017. While the building plans are consistent with the DP as it relates to the zoning review purview of the building footprint, building height, square footage, site conditions etc., zoning cannot approve the building plans until the DP is approved and all PDSD Commercial Plans reviewers have approved the building plans. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
| 04/27/2020 | LOREN MAKUS | ENGINEERING | REVIEW | Reqs Change | DP20-0017 must be approved first. |
| 05/13/2020 | PIMA COUNTY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 05/13/2020 | PIMA COUNTY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 05/13/2020 | PIMA COUNTY | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Reviewer: Charlie Bard 1. Provide Geotechnical Report. BUILDING 1. . Building area for this building use M and VB 36,000 show how you determined the amount of increase to get 42,300. 2. The exit lighting is showed at the back and side door, why is there not an exit sign for the front door. 3. PROVIDE NOTE BELOW UNDER THE CODE ANALYSIS DATA: ( page T1.1) The aggregate quantity of material stored or displayed in a single control area of group M occupancy shall not exceed the quantities in Table 414.2.5(1). The material stored in this building addition are not classify under group H. |
| 05/13/2020 | PIMA COUNTY | WATER | REVIEW | Passed | |
| 05/13/2020 | PIMA COUNTY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 05/13/2020 | JGARCIA1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed |