Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM01797
Parcel: 107031860

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM01797
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/06/2020 MARTIN BROWN FIRE REVIEW Approved
04/07/2020 KROBLES1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/10/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/10/2020 ROBERT SHERRY WATER REVIEW Completed
04/10/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
04/27/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet 1.1; Code Analysis: The Occupancy Group is listed as M (Mercantile/Wholesale). But the occupant load for the entire building is calculated using 500 SF/occupant (a Warehouse function). Please evaluate the function of this space. Per Table 1004.5, Mercantile occupancy load is 60 SF/occupant, office occupancy load is 150 SF/occupant, and mercantile storage occupancy load is 300 SF/occupant.
2. Sheet 1.1; Code Analysis: The number of exits is listed as 2 per Table 1006.3.2. However, Section 1006.3.3 and Tables 1006.3.3(1) and 1006.3.3(2) indicate when one exit is adequate. These Tables should be used in combination with Table 1006.2.1. Please revise this sheet (2 exits are still required).
3. Sheet 2.2; Wall Legend: Please indicate in the Wall Legend the spacing of the new wall studs and the total construction of those walls (gyp. bd, insulation, etc.).
4. Sheet 2.2; Wall Legend: Please indicate on this sheet (using details or notes) how the lateral design requirements of the Section 1607.15 are met (some go to the roof).
5. Sheet 2.2; Floor Plan: There are corridors indicated on the Floor Plan. Using Table 1020.1, verify if those corridors are required to have a one hour fire resistance rating for the B or M Occupancy Classification.
6. Sheet 3.1; Reflected Ceiling Plan: Please indicate the exit signs on the plan.
7. General: Please provide written responses to all review comments.
04/27/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved