Permit Number: T20CM01782
Parcel: 110055550

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM01782
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/01/2020 MARTIN BROWN FIRE REVIEW Approved
04/08/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. If P-1 is intended to have a common vent with P-2, remove the 1-1/2" vent over P-2. If a common vent is not intended, the fixture drain from P-1 cannot connect to the vent for P-2. Reference: Sections 901.4 and 911.3, IPC 2018.
2. Revise the hot water supply to P-1 to comply with the maximum distance requirements of Section C404.5, IECC 2018.
04/08/2020 ROBERT SHERRY WATER REVIEW Completed
04/09/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
04/22/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/22/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A2.0; Dimensioned Floor Plan: Wall Type F between Offices 1 and 2 and between Office 1 and the Restroom shows up as a new partition and an existing partition. Please provide verbiage to better identify Wall Type F.
2. Sheet A2.0; Dimensioned Floor Plan: There is a small t-section of wall between the Breakroom, Office 2, and the Hall that have no Wall Types identified. Please provide.
3. Sheet A2.1 (Floor Plan); Sheet A4.0 (Details 7 and 13): Detail 7 indicates a double stud wall at the plumbing wall, while the Detail 13 indicates a single stud wall. Note 6 of Detail 7 indicates staggered metal studs per Floor Plan. This is Wall Type E on Sheet A2.0, which makes no mention of a double stud wall. Please clarify on the drawings.
4. General: Please provide written responses to all review comments.
04/23/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide receptacle placement in the conference room as required per NEC 201.71B(1), (2).
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code.