Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM01782
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/01/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 04/08/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. If P-1 is intended to have a common vent with P-2, remove the 1-1/2" vent over P-2. If a common vent is not intended, the fixture drain from P-1 cannot connect to the vent for P-2. Reference: Sections 901.4 and 911.3, IPC 2018. 2. Revise the hot water supply to P-1 to comply with the maximum distance requirements of Section C404.5, IECC 2018. |
| 04/08/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 04/09/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 04/22/2020 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 04/22/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A2.0; Dimensioned Floor Plan: Wall Type F between Offices 1 and 2 and between Office 1 and the Restroom shows up as a new partition and an existing partition. Please provide verbiage to better identify Wall Type F. 2. Sheet A2.0; Dimensioned Floor Plan: There is a small t-section of wall between the Breakroom, Office 2, and the Hall that have no Wall Types identified. Please provide. 3. Sheet A2.1 (Floor Plan); Sheet A4.0 (Details 7 and 13): Detail 7 indicates a double stud wall at the plumbing wall, while the Detail 13 indicates a single stud wall. Note 6 of Detail 7 indicates staggered metal studs per Floor Plan. This is Wall Type E on Sheet A2.0, which makes no mention of a double stud wall. Please clarify on the drawings. 4. General: Please provide written responses to all review comments. |
| 04/23/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide receptacle placement in the conference room as required per NEC 201.71B(1), (2). Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code. |