| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/10/2020 | SAMUEL ROGERS | ZONING | REVIEW | Approved | |
| 06/11/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/15/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Comment not resolved. See figure 408.4, IFGC 2018 for the required geometry of the sediment trap. [Initial comment: Revise the configuration of the natural gas sediment trap, as shown in detail 5/P6.00 to comply with the requirements of Section 408.4, IFGC 2018 (i.e. the sediment trap is to be located downstream of the appliance shutoff valve, as close to the appliance as possible and the flow of the gas not proceeding straight along the run of the tee).] |