Permit Number: T20CM01769
Parcel: 13418113B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM01769
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/26/2020 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Section Manager

PROJECT: 7444 E Broadway Blvd - Residential Care Services - Unlimited
T20CM01769
Building plan.

TRANSMITTAL DATE: March 20, 2020

The development package has been reviewed by the Zoning Review Section for minimal compliance with the Administrative Manual Section 2-06. It has been determined that the submitted plans do not provide sufficient information to complete a plan review. The following items need to be addressed prior to re-submittal.

1. Under "GENERAL ZONING ANALYSIS" provide the proposed use. This use should be Residential Care Services, Adult Care or Physical and Behavioral Health Services: Unlimited # of Residents subject to Use Specific Standards 4.9.7.J.3.d, .4, & .8 and 4.9.13.O.

2. Per UDC 7.9.7.J.8 The maximum permitted lot coverage is 60%. The minimum required setback from all interior lot lines adjoining residential zoning is 20 feet. The minimum required lot size is one and one-half acres, with the following exception. Exception: There is no minimum lot size requirement for Residential Care Services uses in the R-3, C-1, C-2, C-3, OCR-1, and OCR-2 zones. Provide a lot coverage calculation on the plan, see UDC Article 6.4.3.

3. As a note, provide calculations on the number of vehicle parking spaces required (include the ratio used) and the number provided, including the number of spaces required and provided for the physically disabled.

4. The accessible vehicle parking spaces shown on sheet A1.11 do not appear to meet the requirements of 2018 IBC Chapter 11 and the ICC A117.1-2009. Although it is not a requirement to upgrade the accessible vehicle parking spaces it is strongly recommended.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
04/01/2020 MARTIN BROWN FIRE REVIEW Approved
04/06/2020 ROBERT SHERRY WATER REVIEW Completed
04/07/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. If the showers do not have a pre-fabricated receptors, provide details to show that the construction of the receptor complies with the requirements of Section 421.5, IPC 2018.
2. Provide metering faucets for the public lavatories, dispensing a maximum of 0.25 gallons per metering cycle (not 0.25 GPM). Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
3. Tucson Water records indicate that the water pressure for this address will range from 78 to 85 PSI. Provide a water pressure regulator conforming to ASSE 1003 or CSA B356 to limit the water pressure to 80 PSI or less. Reference: Section 604.8, IPC 2018.
4. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves (e.g. dishwashers). The pressure-absorbing devices shall conform to ASSE 1010; an air chamber is not acceptable. Reference: Section 604.9, IPC 2018.
5. The discharge temperature of the proposed dishwasher will be greater than 140 degrees Fahrenheit; show that the temperature rating of the drainage pipe material is suitable for the highest temperature of the wastewater or provide a drain water tempering kit with the dishwasher. Reference: Section 702.5, IPC 2018.
6. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.
7. Based on Table 402.4(2(, IFGC 2018, the size of the pipe serving P27 should be 1-1/4" (240 MBH @ 200 feet TDL). Reference: Sections 402.1 and 402.3, IFGC 2018.
8. Revise the configuration of the natural gas sediment trap, as shown in detail 5/P6.00 to comply with the requirements of Section 408.4, IFGC 2018 (i.e. the sediment trap is to be located downstream of the appliance shutoff valve, as close to the appliance as possible and the flow of the gas not proceeding straight along the run of the tee).
04/09/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
04/21/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
04/27/2020 LOREN MAKUS ENGINEERING REVIEW Passed
04/30/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A0.21; Plumbing Fixture Calculations (Bathtubs/showers): The rounded total indicates 5, while there are 4 provided. Please clarify.
2. Sheet A0.21; Code Data (Fire Protection): Per the IBC Section 420.5, a smoke alarm is required. Please indicate that on this sheet.
3. Sheet A0.31; Fire Resistance Plan: Please verify on this drawing the requirements of the IBC Section 420.8(1), (3), (4), (5), (6), (7), (8), and (9) are met.
4. Sheet A0.31 (Fire Resistive Plan); Rating Legend: This Legend seems to indicate all dark walls are fire partitions (1 hour rated per note), and all light walls are 1 hour rated per the Legend. Please clarify for all rated walls.
5. Sheet S2.11; Framing Keynotes: The roof girder down the center portion of the building has a framing keynote 8. Please revise that note number for the girder.
6. General: Please provide a Special Inspection Certificate with Parts A and B completed. This may be found on the City of Tucson website www.tucsonaz.gov/PDSD.
7. General: Please provide written responses to all review comments.
04/30/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
06/09/2020 KROBLES1 OUT TO CUSTOMER Completed
06/05/2020 ARAMIRE4 REJECT SHELF Completed