| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/16/2020 | DJELLEN1 | ZONING | REVIEW | Reqs Change | FROM: David Jellen PDSD Zoning Review Section PROJECT: T20CM01720 Building Plan Review (1st Review) / Relate to DP20-0037 5150 E Speedway / C-2 Zoning TRANSMITTAL DATE: March 16, 2020 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage and location to ensure consistency with the DP. 2. COMMENT: Once the plans have been reviewed and approved by PDSD Commercial Plan Reviewers and zoning has verified consistency with the DP, the building plans can be approved by zoning. If you have any questions about this transmittal, contact David Jellen at (520) 837-4082 or by email at David.Jellen@tucsonaz.gov. |
| 03/16/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide an energy analysis (e.g. COMcheck) for the building addition. 2. Provide HVAC cooling/heating load calculations. |
| 03/16/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan recommends. Also provide a written response. 1. Provide exterior luminaire manufacturer cut sheets that correlate with the luminaire schedule in order to verify the luminaire compliance for color temperature and lumen output. 2. Provide a complete luminaire schedule for all new or replaced lighting. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code. |
| 03/16/2020 | DJELLEN1 | ENGINEERING | REVIEW | Reqs Change | Engineering cannot approve until DP20-0037 has been approved. |
| 03/16/2020 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/16/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 03/16/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | |
| 03/16/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 03/16/2020 | RMCCOY1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |