Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/11/2020 DJELLEN1 ZONING REVIEW Approved
03/11/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide data to show that the proposed walk-in freezer and the proposed walk-in cooler meet the construction and efficiency requirements of Sections C403.10.2 and C403.10.2.1, IECC 2018.
03/11/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
03/11/2020 DJELLEN1 ENGINEERING REVIEW Passed
03/11/2020 RMCCOY1 BUILDING-COMMERCIAL REVIEW Approved
03/11/2020 ROBERT SHERRY WATER REVIEW Completed
03/11/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify that the hub drain (detail 2/P1.1) is not located in a concealed location and that it has ready access. Reference: Section 802.4, IPC 2018.
2. The J R Smith trap seal does not appear to be listed for use in a hub drain. Reference: Section 303.2, IPC 2018.
3. Island venting is limited to sinks and lavatories, not other fixtures (details 3 and 4/P1.1). Refernce: Section 916.1, IPC 2018.
03/11/2020 RMCCOY1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/12/2020 MARTIN BROWN FIRE REVIEW Reqs Change Code analysis indicates occupant load has increased to over 100 occupants. A-2 occupancies with a load of over 100 require fire sprinklers. Revise cover sheet to clearly indicate the occupant load will not increase over current levels, or add note indicating fire sprinkler will be required.