Review Details: COMMERCIAL - TI
Permit Number - T20CM01634
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/11/2020 | DJELLEN1 | ZONING | REVIEW | Approved | |
| 03/11/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide data to show that the proposed walk-in freezer and the proposed walk-in cooler meet the construction and efficiency requirements of Sections C403.10.2 and C403.10.2.1, IECC 2018. |
| 03/11/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/11/2020 | DJELLEN1 | ENGINEERING | REVIEW | Passed | |
| 03/11/2020 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/11/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 03/11/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Verify that the hub drain (detail 2/P1.1) is not located in a concealed location and that it has ready access. Reference: Section 802.4, IPC 2018. 2. The J R Smith trap seal does not appear to be listed for use in a hub drain. Reference: Section 303.2, IPC 2018. 3. Island venting is limited to sinks and lavatories, not other fixtures (details 3 and 4/P1.1). Refernce: Section 916.1, IPC 2018. |
| 03/11/2020 | RMCCOY1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/12/2020 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | Code analysis indicates occupant load has increased to over 100 occupants. A-2 occupancies with a load of over 100 require fire sprinklers. Revise cover sheet to clearly indicate the occupant load will not increase over current levels, or add note indicating fire sprinkler will be required. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/09/2020 | ARUIZ1 | OUT TO CUSTOMER | Completed |