Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM01596
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/10/2020 | DJELLEN1 | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: David Jellen Planning and Development Services PROJECT: T20CM01596 340 N. Main Ave Interior Tenant Improvement with Exterior Window Filling TRANSMITTAL: March 10, 2020 COMMENTS: the following comments are relative to an application for Historic Review (UDC 5.8.8). This site is located in the HO-3 zone (UDC 4.7.15). Exterior changes to the building must go through Historic Review. Zoning cannot approve until Historic Review has been approved. |
| 03/10/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Revise the natural ventilation notes for offices 3 and 4 - there are no doors opening to the outside. Give the area of any operable windows. |
| 03/10/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/10/2020 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
| 03/10/2020 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Provide the code analysis for the minimum required plumbing fixtures . IBC Chap. 29. |
| 03/10/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 03/10/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 03/10/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 03/10/2020 | RMCCOY1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/13/2020 | JWILLIA2 | OUT TO CUSTOMER | Completed |