Permit Number: T20CM01570
Parcel: 11105063J

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM01570
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/11/2020 SAMUEL ROGERS ZONING REVIEW Approved
03/11/2020 SROGERS2 ENGINEERING REVIEW Passed
03/11/2020 RMCCOY1 BUILDING-COMMERCIAL REVIEW Reqs Change Provide structural calculations for exhaust fan support frame .
03/11/2020 RMCCOY1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/17/2020 ROBERT SHERRY WATER REVIEW Completed
03/17/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The 2" drain from the sump pump (not including the multiple condensate pumps) is undersized. Reference: Section 709.3, IPC 2018.
2. Coordinate detail 202 with the plumbing plan.
03/19/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
03/24/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
03/24/2020 MARTIN BROWN FIRE REVIEW Approved