Permit Number: T20CM01568
Parcel: 117150010

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM01568
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/08/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Revise the CW and Building steel bonding conductor sizes to comply with NEC 250.102C1 and 240.104 or justify the size shown on the line diagram.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.