Review Date Reviewer's Name Type of Review Description Status Comments
03/09/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan recommends. Also provide a written response.
1. Provide a note on the plans describing the scope of work for the proposed electrical work and any structural, also indicate with a cloud or assign the correlating Delta to the changes.
2. Indicate what is new and what is existing.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.