Permit Number: T20CM01503
Parcel: 107112220

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM01503
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/29/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet CVR: Please provide a Code Analysis on this sheet (Occupancy Classification S-2/Construction Type IIIB).
2. Sheet CVR; Code Edition: Please revise the Code Edition to the 2018 IBC.
3. Sheet CVR: Please indicate on this sheet to follow the IBC Section 107.3.4.1 for deferred submittal requirements.
4. General: Please provide structural calculations for this project.
5. General: Please provide written responses to all review comments.
05/29/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved