Permit Number: T20CM01492
Parcel: 10408092B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM01492
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/17/2020 MARTIN BROWN FIRE REVIEW Approved
03/23/2020 RMCCOY1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/23/2020 RMCCOY1 BUILDING-COMMERCIAL REVIEW Reqs Change 1.Provide a completed Special Inspection Form for - Periodic Special Inspection For Post Installed Epoxy Rebar Or Anchors - .# 13 Sheet S1, IBC107.2.1.
03/31/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
03/31/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide roof drainage calculations for the new canopy.
2. Clarify the enlarged front entry plan on A1.3. It appears like the new 2" rainwater leader is being connected to an existing 4" overflow rainwater leader on the east side of entry. Primary rainwater leaders and overflow rainwater leaders may not be combined, Reference: Section 1108.1, IPC 2018.
03/31/2020 ROBERT SHERRY WATER REVIEW Completed
04/07/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
04/14/2020 SSHIELD1 ENGINEERING REVIEW Passed
04/14/2020 STEVE SHIELDS ZONING REVIEW Approved