Permit Review Detail
Review Status: Completed
Review Details: WALK THRU - COMM
Permit Number - T20CM01442
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/03/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Ref; Plan Sheet E-3. (a) Violation of NEC 230.2. One service per building. (b) Indicate all feeder sizes and types. (c) Indicate new or existing. (d) Indicate which wireway is #1 and #2. (e) Verify compliance with NEC 250.3 (f) Why does the 3-4" secondarys tie into the wireway first and not the term can? (g) Note #16. What is a TC Can? (h) For clarity, provide a note indicating the scope of work in detail. Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal requirements. |