Permit Number: T20CM01433
Parcel: 141185940

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM01433
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/16/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/16/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Comment not addressed. [Initial comment: Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported from the building structure. Reference: Section 301.2, IPC 2018.]
04/16/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Comment not addressed. [Initial comment: 1. The ventilation of the dog room requires mechanical ventilation with no recirculation of the air from the space into other areas. The exhaust fan is controlled by a time clock that will shut down during non-occupied times thus cauing the supply air to the dog room to be recirculated to the rest of the building. In addtion, the balancing data shows 325 CFM of supply to the room with only 155 CFM of exhaust. Reference: Footnote b, Table 403.3.1.1, IMC 2018.]