Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM01433
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/16/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/16/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Comment not addressed. [Initial comment: Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported from the building structure. Reference: Section 301.2, IPC 2018.] |
| 04/16/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Comment not addressed. [Initial comment: 1. The ventilation of the dog room requires mechanical ventilation with no recirculation of the air from the space into other areas. The exhaust fan is controlled by a time clock that will shut down during non-occupied times thus cauing the supply air to the dog room to be recirculated to the rest of the building. In addtion, the balancing data shows 325 CFM of supply to the room with only 155 CFM of exhaust. Reference: Footnote b, Table 403.3.1.1, IMC 2018.] |