Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T20CM01433
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/04/2020 | NMARTEL1 | ZONING | REVIEW | Approved | |
| 03/10/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 03/17/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported from the building structure. Reference: Section 301.2, IPC 2018. 2. Verify that the distance from the hot water source to the hot water termination for the public lavatory complies with the requirements of Section C404.5, IECC 2018. |
| 03/17/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. The ventilation of the dog room requires mechanical ventilation with no recirculation of the air from the space into other areas. The exhaust fan is controlled by a time clock that will shut down during non-occupied times thus cauing the supply air to the dog room to be recirculated to the rest of the building. In addtion, the balancing data shows 325 CFM of supply to the room with only 155 CFM of exhaust. Reference: Footnote b, Table 403.3.1.1, IMC 2018. 2. Provide an exhaust vent for the clothes dryer. Reference: Section 504.1, IMC 2018. |
| 03/22/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Previous Comment 1; Sheet A2.0; Reflected Ceiling Plan: Please revise the title of this plan to indicate Reflected Ceiling Plan. 2. Sheet A2.0; Wall Types: Wall Types A and D reference Details 13/A9.0 and 14/A9.0. Please revise those detail references. 3. Previous Comment 3; Sheet A5.0; Detail 13: Please remove the reflected ceiling plan dimension on the right side of the detail. 4. Previous Comment 4; General: Please provide written responses to all review comments. |