Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM01433
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/03/2020 | LSHAMIS1 | ZONING | REVIEW | Reqs Change | Vet clinic building cannot be within 200 feet of a residential zone per use-specific standard 4.9.4.D.7. Loran Shamis loran.shamis@tucsonaz.gov |
| 03/03/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide an exhaust vent for the clothes dryer. |
| 03/03/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/03/2020 | LSHAMIS1 | ENGINEERING | REVIEW | Passed | |
| 03/03/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A2.0; Reflected Ceiling Plan: Please revise the title for this plan. 2. Sheet A2.0; Wall Types: Is Wall D required to be a fire resistance rated wall per the IBC Section 708(2)? Please verify. 3. Sheet A5.0; Detail 13: Remove the RCP dimension note indication on the right side of the detail. 4. General: Please provide written responses to all review comments. |
| 03/03/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 03/03/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Revise the hot water supply to the restroom lavatory to limit the distance from the hot water source to 24" per Section C404.5, IECC 2018. |
| 03/03/2020 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/04/2020 | AMARTIN1 | FIRE | REVIEW | Needs Review |