Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM01432
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/03/2020 | LSHAMIS1 | ZONING | REVIEW | Approved | |
| 03/03/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 03/03/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/03/2020 | LSHAMIS1 | ENGINEERING | REVIEW | Passed | |
| 03/03/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A2.0; Wall Types: Is Wall C required to be a fire resistance rated wall per the IBC Section 708(2)? Please verify. 2. Sheet A2.0; Floor Plan: Access to the restroom goes through a storage area. Does the IBC Section 1016.2(5)(2) allow this? Please verify. 3. Sheet A5.0; Detail 11: Please revise this detail to match Detail 205 on Sheet P2.0. 4. General: Please provide written responses to all review comments. |
| 03/03/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 03/03/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide anchoring details for the water heater support. |
| 03/03/2020 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/31/2020 | MARTIN BROWN | FIRE | REVIEW | Approved |