Permit Number: T20CM01362
Parcel: 120091360

Address:
407 E RODEO DR

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM01362
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2020 SAMUEL ROGERS ZONING REVIEW Needs Review ZONING REVIEW TRANSMITTAL

FROM: Samuel Rogers
Planner

PROJECT:
T20CM01362
407 E Rodeo Dr.
Porch Addition

TRANSMITTAL: 2/28/2020
COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A).

The project is a porch addition with a maximum post height of 8' requiring a minimum setback of 6' on the east property line. The proposed east side setback is 3'. A DDO is required.
02/28/2020 LOREN MAKUS ENGINEERING REVIEW Passed
03/11/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change THE 4" X 6" BEAM IS UNDERSIZED FOR THE 11' - 8" SPAN

K. E. VAN KARSEN
520 837-4912