Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T20CM01354
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/11/2020 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Needs Review | Provide a complete plan set for review. See the helpful links "Residential Submittal Requirements" at https://www.tucsonaz.gov/pdsd/residential-permits K E Van Karsen 520 837-4912 |
| 03/26/2020 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
| 03/31/2020 | SAMUEL ROGERS | ZONING | REVIEW | Reqs Change | FROM: Samuel Rogers – Planner PDSD Zoning Review Section PROJECT: T20CM01354 Single Family Addition (1st Review) 450 S Via Golondrina TRANSMITTAL DATE: 3/31/2020????? DUE DATE: 3/27/2020????? COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. COMMENT: The proposed structure does not meet setback requirements for the RX-1 zone. The storage room must be a minimum of 20' from all property lines. The proposed setbacks are 10.33' on the northwest property line and 16.6' on the southwest property line. A Design Development Option (DDO) will be required to allow for the proposed setbacks. You can find the DDO application online at https://www.tucsonaz.gov/files/pdsd/2019_DDO_for_Setback_and_Height_UDC.pdf If you have any questions about this transmittal, contact Samuel Rogers at Samuel. Rogers@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans |