Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM01338
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/09/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
09/14/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Per the response to the Electrical plan review comment # 3 for the location of label #5 (Rapid Shutdown). The response indicated that the label is to be applied to the inverters. Since the inverters are located remotely from the electrical service equipment, provide a label located within 3 feet of the service equipment describing the location of the rapid shutdown initiation devices as required per NEC 690.56C(1). 2. The site plan shows the electrical service equipment as new. The electrical roof plan shows the electrical service as existing. Please clarify. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |