Permit Number: T20CM01338
Parcel: 125011200

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T20CM01338
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/11/2020 MARTIN BROWN FIRE REVIEW Approved
03/13/2020 RMCCOY1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/13/2020 RMCCOY1 BUILDING-COMMERCIAL REVIEW Reqs Change Plans are stamped - " Not To Be Used For Construction " - ; submit plans to be used for construction . IBC107..2.1.
03/31/2020 LOREN MAKUS ENGINEERING REVIEW Passed
04/01/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide detailed information including hardware for the load side tap at the existing panel.
2. Provide complete information for the existing electrical service, amp, AIC, Main breaker ratings, voltage, phase. Is the main breaker at the service equipped with GFI protection?
3. Indicate where Warning Label #5 is to be applied.
4. Provide a grounding detail for the racking.
5. Some of electrical plans are stamped, "NOT FOR CONSTRUCTION".
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/31/2020 VLEON1 APPROVAL SHELF Completed
08/31/2020 VLEON1 OUT TO CUSTOMER Completed
08/31/2020 VLEON1 REJECT SHELF Completed