Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T20CM01338
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/11/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 03/13/2020 | RMCCOY1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/13/2020 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Plans are stamped - " Not To Be Used For Construction " - ; submit plans to be used for construction . IBC107..2.1. |
| 03/31/2020 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
| 04/01/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide detailed information including hardware for the load side tap at the existing panel. 2. Provide complete information for the existing electrical service, amp, AIC, Main breaker ratings, voltage, phase. Is the main breaker at the service equipped with GFI protection? 3. Indicate where Warning Label #5 is to be applied. 4. Provide a grounding detail for the racking. 5. Some of electrical plans are stamped, "NOT FOR CONSTRUCTION". Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/31/2020 | VLEON1 | APPROVAL SHELF | Completed |
| 08/31/2020 | VLEON1 | OUT TO CUSTOMER | Completed |
| 08/31/2020 | VLEON1 | REJECT SHELF | Completed |