| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/24/2020 | TOM WEIDEMAN | ZONING | REVIEW | Completed | |
| 02/24/2020 | TOM WEIDEMAN | ENGINEERING | REVIEW | Completed | |
| 02/27/2020 | TWEIDEM1 | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | 1. Show the sum of the main and backfeed breakers not exceeding 120% of the busbar (and conductor) rating, NEC 690.64 & 705.12 (D). All conductive components between the energy source breakers require this rating. Tom Weideman 520-837-6823 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/27/2020 | TWEIDEM1 | APPROVAL SHELF | Completed |
| 02/27/2020 | TWEIDEM1 | OUT TO CUSTOMER | Completed |
| 02/27/2020 | TWEIDEM1 | REJECT SHELF | Completed |