Permit Review Detail
Review Status: Active
Review Details: REVISION - - 1ST
Permit Number - T20CM01209
Review Name: REVISION - - 1ST
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/03/2020 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: Steve Shields Section Manager PROJECT: T20CM01209 ADA Parking Upgrades CVS - 3832 E Speedway Blvd TRANSMITTAL DATE: September 3, 2020 DUE DATE: September 2, 2020 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. Per ICC A117.1, Section 502.5 access aisles shall not have slopes steeper than 1:48. The proposed asphalt overlays will not work with the 4.5% slope. Provide a accessible ramp that is not within the access aisle. 2. Sheet AS3 detail 4 demonstrate that all minimum clearances are maintained from the west end of the access aisle to the building column. Per COT Technical Standards Manual the minimum width is 4'-0" clear. If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package |