Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM01209
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/04/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
03/16/2020 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Approved | |
03/16/2020 | RMCCOY1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
03/20/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
03/20/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
03/20/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
03/26/2020 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
04/01/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide complete compliance with the 2018 IECC for the lighting. ComCheck is acceptable. 2. Provide for compliance with NEC 517.13 for exam room wiring if applicable. 3. Provide for tamper resistant receptacles as applicable per NEC 406.12. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |