Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM01208
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/04/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 03/16/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A000; Project Data (Means of Egress): The number of exits indicates 2 per the IBC Table 1006.3.2. However, using Section 1006.3.3 along with Table 1006.3.3(2), one exit is allowed if the common path of egress travel does not exceed the indicated distance. Please indicate on this sheet. 2. Sheet A000; Project Data: In addition to the required number of water closets listed on this project, please add (per the IBC Table 2902.1) the required number of lavatories, service sinks, and drinking fountains to this sheet. 3. Sheets A001, D101, A101, A201, and A601; Plans: Please add north arrows to these plans. 4. Sheet A101 (Floor Plan); Sheet A102 (Wall Types): The Wall Types 1, 1A, 2B, 7, and 7A shown on Sheet A102 were not located on the Floor Plan. Please verify. 5. Sheet A201 (Reflected Ceiling Plan); Key Legend: The Key Legend indicates exit signs, but those are not shown on the Reflected Ceiling Plan. Please verify. 6. Sheet A400; Interior Elevation 4: Please provide the dimension from the floor to the bottom of the vertical grab bar per the ICC/ANSI Figure 604.5.1. 7. Sheet P-100; Keyed Note 2: This note indicates to reference to the architectural plans for the water heater shelf requirements. Please indicate a detail for the water heater support on the architectural or plumbing sheets. 8. General: Please provide written responses to all review comments. Review by Eric Newcomb Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov |
| 03/16/2020 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/20/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Tucson Water data indicates that the water pressure range for this address is 35-42 PSI. Verify that the water distribution system can provide adequate pressure to the fixtures. Reference: Section 604.7, IPC 2018. 2. Show how the distance from the hot water source to the hot water termination for the public lavatories will comply with the requirements of Section C404.5, IECC 2018. |
| 03/20/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 03/20/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 03/26/2020 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
| 04/01/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/22/2020 | LBOWERS1 | OUT TO CUSTOMER | Completed |