Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T20CM01208
Parcel: 136406780

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM01208
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/04/2020 MARTIN BROWN FIRE REVIEW Approved
03/16/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A000; Project Data (Means of Egress): The number of exits indicates 2 per the IBC Table 1006.3.2. However, using Section 1006.3.3 along with Table
1006.3.3(2), one exit is allowed if the common path of egress travel does not exceed the indicated distance. Please indicate on this sheet.
2. Sheet A000; Project Data: In addition to the required number of water closets listed on this project, please add (per the IBC Table 2902.1) the required number of lavatories, service sinks, and drinking fountains to this sheet.
3. Sheets A001, D101, A101, A201, and A601; Plans: Please add north arrows to these plans.
4. Sheet A101 (Floor Plan); Sheet A102 (Wall Types): The Wall Types 1, 1A, 2B, 7, and 7A shown on Sheet A102 were not located on the Floor Plan. Please verify.
5. Sheet A201 (Reflected Ceiling Plan); Key Legend: The Key Legend indicates exit signs, but those are not shown on the Reflected Ceiling Plan. Please verify.
6. Sheet A400; Interior Elevation 4: Please provide the dimension from the floor to the bottom of the vertical grab bar per the ICC/ANSI Figure 604.5.1.
7. Sheet P-100; Keyed Note 2: This note indicates to reference to the architectural plans for the water heater shelf requirements. Please indicate a detail for the water heater support on the architectural or plumbing sheets.
8. General: Please provide written responses to all review comments.

Review by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
03/16/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/20/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Tucson Water data indicates that the water pressure range for this address is 35-42 PSI. Verify that the water distribution system can provide adequate pressure to the fixtures. Reference: Section 604.7, IPC 2018.
2. Show how the distance from the hot water source to the hot water termination for the public lavatories will comply with the requirements of Section C404.5, IECC 2018.
03/20/2020 ROBERT SHERRY WATER REVIEW Completed
03/20/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
03/26/2020 LOREN MAKUS ENGINEERING REVIEW Passed
04/01/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/22/2020 LBOWERS1 OUT TO CUSTOMER Completed