Permit Number: T20CM01186
Parcel: 12809005G

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T20CM01186
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/10/2020 MARTIN BROWN FIRE REVIEW Approved
03/12/2020 TOM WEIDEMAN ZONING REVIEW Reqs Change
03/13/2020 RMCCOY1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/13/2020 RMCCOY1 BUILDING-COMMERCIAL REVIEW Reqs Change Cooridinate the structural calculations with plans for the - Columns , Footings , Purlins , and connections etc.. IBC107.2.1.
03/17/2020 LOREN MAKUS ENGINEERING REVIEW Reqs Change DP must be approved first.
03/24/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Ref; West System.
(a) The pull box utilized cannot contain both PV Output circuits and other non-PV circuit. NEC 690..31B.
(b) Removing a Bucket in the service equipment to accommodate space for the PV interconnection may void the listing of the existing equipment. Provide for a qualified NRTL field evaluation after the tap or interconnection is performed to ensure the listing of the service equipment is not compromised.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/08/2020 KROBLES1 OUT TO CUSTOMER Completed
04/08/2020 MRESS1 REJECT SHELF Completed