| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/10/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 03/12/2020 | TOM WEIDEMAN | ZONING | REVIEW | Reqs Change | |
| 03/13/2020 | RMCCOY1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/13/2020 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Cooridinate the structural calculations with plans for the - Columns , Footings , Purlins , and connections etc.. IBC107.2.1. |
| 03/17/2020 | LOREN MAKUS | ENGINEERING | REVIEW | Reqs Change | DP must be approved first. |
| 03/24/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Ref; West System. (a) The pull box utilized cannot contain both PV Output circuits and other non-PV circuit. NEC 690..31B. (b) Removing a Bucket in the service equipment to accommodate space for the PV interconnection may void the listing of the existing equipment. Provide for a qualified NRTL field evaluation after the tap or interconnection is performed to ensure the listing of the service equipment is not compromised. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/08/2020 | KROBLES1 | OUT TO CUSTOMER | Completed |
| 04/08/2020 | MRESS1 | REJECT SHELF | Completed |