Permit Number: T20CM01183
Parcel: 13101013E

Address:
5480 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM01183
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/21/2020 NMARTEL1 ZONING REVIEW Passed
02/21/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide HVAC heating/cooling load calculations to justify the capacities of the new AC units.
2. Update the energy code compliance information to include the refrigerated display cases, walk-in freezers, and walk-in coolers. See Section C403.10, IECC 2018.
02/21/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please Provide a complete electrical panel schedule include load calcs.
02/21/2020 NMARTEL1 ENGINEERING REVIEW Passed
02/21/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/21/2020 ROBERT SHERRY WATER REVIEW Completed
02/21/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
02/21/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
03/02/2020 MARTIN BROWN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/23/2020 ARUIZ1 APPROVAL SHELF Completed
03/23/2020 ARUIZ1 OUT TO CUSTOMER Completed
03/23/2020 ARUIZ1 REJECT SHELF Completed