Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM01183
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/21/2020 | NMARTEL1 | ZONING | REVIEW | Passed | |
| 02/21/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide HVAC heating/cooling load calculations to justify the capacities of the new AC units. 2. Update the energy code compliance information to include the refrigerated display cases, walk-in freezers, and walk-in coolers. See Section C403.10, IECC 2018. |
| 02/21/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please Provide a complete electrical panel schedule include load calcs. |
| 02/21/2020 | NMARTEL1 | ENGINEERING | REVIEW | Passed | |
| 02/21/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/21/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 02/21/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 02/21/2020 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
| 03/02/2020 | MARTIN BROWN | FIRE | REVIEW | Approved |