Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T20CM01179
Parcel: 12109006A

Address:
5151 E PIMA ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM01179
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/04/2020 MARTIN BROWN FIRE REVIEW Approved
03/12/2020 RMCCOY1 BUILDING-COMMERCIAL REVIEW Approved
03/23/2020 ELISA HAMBLIN ZONING REVIEW Reqs Change FROM: Iman Monshizadeh

PDSD Zoning Review Section



PROJECT: T20CM01179 (Project Number)

Interior Remodel and Demo (1st Review)

5151 N Pima



TRANSMITTAL DATE: 3/23/2020



DUE DATE: 3/26/2020



COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.





COMMENT: New fences proposed on the property will need to be reflected on the Development Package. A revision for the Development Package will need to be approved prior to zoning approval. The Development Package review will be minor and zoning is willing to do a digital over the counter review if requested.





If you have any questions about this transmittal, Contact Iman Monshizadeh at Iman.monshizadeh@tucsonaz.gov
03/26/2020 LOREN MAKUS ENGINEERING REVIEW Passed
03/31/2020 RMCCOY1 ELECTRICAL-COMMERCIAL REVIEW Approved
04/03/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide the ventilation schedule indicated in flag note 1 on sheet M3.00. Reference: Section 107.2.1, IBC 2018.
04/03/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Correct the water calculations on sheet P1.00. The calculations are for the City of Chandler; the meter size and water pressure in the main are incorrect. Reference: Section 107.2.1, IBC 2018.
2. Verify that the specified sensor faucet for the public lavatories has an automatic time-out so that it will dispense a maximum of 0.25 gallons per metering cycle. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
3. Verify that the tempered water for the public restroom lavatories is provided using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2018.
4. Verify that the distance from the hot water source (the hot water recirculation loop) to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.
04/03/2020 ROBERT SHERRY WATER REVIEW Completed