Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM01167
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/20/2020 | IMONSHI1 | ZONING | REVIEW | Approved | |
| 02/20/2020 | IMONSHI1 | ENGINEERING | REVIEW | Passed | |
| 02/20/2020 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Completed | |
| 02/20/2020 | RMCCOY1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 02/21/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 02/25/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the HVAC to avoid using the egress corridor as a duct. 2. The existing area was required to have ventilation. Show the required amount of ventilation and the air flow rates for each diffusers. |
| 02/25/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide specification for the new sink. 2. Provide a trap for the new sink. 3. Where is the existing water heater located (i.e. how far is the hot water source from the new sink). |
| 02/25/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 02/25/2020 | ROBERT SHERRY | WATER | REVIEW | Completed |