Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM01157
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/20/2020 | DJELLEN1 | ZONING | REVIEW | Approved | |
| 02/20/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 02/20/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide a complete panel schedule showing the insta hot water heater. Include load calcs. Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal requirements. |
| 02/20/2020 | DJELLEN1 | ENGINEERING | REVIEW | Passed | |
| 02/20/2020 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Completed | |
| 02/20/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 02/20/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 02/20/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 02/20/2020 | RMCCOY1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |