Permit Number: T20CM01151
Parcel: 119031700

Address:
3003 S 12TH AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM01151
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/05/2020 ANDREW CONNOR ZONING REVIEW Reqs Change FROM: Andrew Connor
Planner

PROJECT: T20CM01151
3003 S 12th Ave.
Attached addition


TRANSMITTAL: March 12, 2020
COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A).

The applicant is proposing a 10' tall attached addition to the South. The required set back according to proposed height of addition is 6.6' from property line. The proposed setback is 3'
03/05/2020 ACONNOR1 ENGINEERING REVIEW Passed
03/05/2020 ANDREW CONNOR NPPO REVIEW Passed
03/11/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Completed