Permit Number: T20CM01118
Parcel: 11504348A

Address:
1120 N 5TH AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM01118
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/19/2020 STEVE SHIELDS ZONING REVIEW Approved
02/19/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Needs Review
02/19/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
02/19/2020 SSHIELD1 ENGINEERING REVIEW Passed
02/19/2020 RMCCOY1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Please provide a life-safety exiting plan; show the exit access to required exits including exit distance and common path of egress travel.
2. The plans do not clearly indicate exiting and new construction of walls/partitions. Please indicate all existing and new construction of walls and partitions.
3. Provide wall/partitions details of attachments to the floor and roof/ceiling. Specify fastener type and installation.
4. Cite all of the adopted codes by the City of Tucson in the CODE REVIEW textbox.
5. The water dispenser station must be accessible for public use as well as employees. The water station must be in a location available to the public as well as employees.
6. Indicate the location of all EXITS.

Please provide written responses to plan review comments.
02/19/2020 ROBERT SHERRY WATER REVIEW Completed
02/19/2020 RMCCOY1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/19/2020 MROSS2 FIRE REVIEW Approved
02/20/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved