Permit Number: T20CM01100
Parcel: 11703180A

Address:
325 W 2ND ST 02

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM01100
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/18/2020 RMCCOY1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/18/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide HVAC load calculations to justify the capacitity of the new heat pumps.
2. Provide COMcheck the mechanical units.
02/18/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
02/18/2020 AHINES2 ENGINEERING REVIEW Passed
02/18/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide the anchoring details for the water heater installation (noted as being provided by the arhitect).
02/18/2020 ROBERT SHERRY WATER REVIEW Completed
02/19/2020 MROSS2 FIRE REVIEW Approved
02/21/2020 RMCCOY1 BUILDING-COMMERCIAL REVIEW Approved
02/25/2020 PMARTIN1 ZONING REVIEW Needs Review