Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/19/2020 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
02/25/2020 | TOM WEIDEMAN | ENGINEERING | REVIEW | Completed | |
02/25/2020 | TWEIDEM1 | NPPO | REVIEW | Passed | |
02/25/2020 | TWEIDEM1 | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | Show the sum of the main and backfeed breakers not exceeding 120% of the busbar (and conductor) rating, NEC 690.64 & 705.12 (D). Consider replacing the service panel with a solar ready device rather than backfeeding to a new sub panel. Tom Weideman Permit Technician City of Tucson 520-837-6823 |