Permit Number: T20CM01078
Parcel: 13018077A

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T20CM01078
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/02/2020 MARTIN BROWN FIRE REVIEW Reqs Change Per table 3206.2 of the 2018 International Fire Code, if the top of storage exceeds 12'-0" AFF, a fire detection system is required. The height of the buiding indicates that this is a possibility. Please add a note to the cover sheet indicating storage will never exceed 12', or that you will install a fire detection system.
03/04/2020 IMONSHI1 ZONING REVIEW Reqs Change FROM: Iman Monshizadeh
PDSD Zoning Review Section

PROJECT: T20CM01078
Shed Addition (1st Review)
2020 S Columbus

TRANSMITTAL DATE: March 4th, 2020

DUE DATE: March 16th, 2020

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


01. COMMENT: A Development Package is required for this shed addition

Submittal requirements: https://www.tucsonaz.gov/files/pdsd/forms/Submittal_Requirements.pdf

Application:https://www.tucsonaz.gov/files/pdsd/forms/Development_Package_and_Land_Division-Subdivision_Application.pdf

02. COMMENT: Once the development package is approved zoning will re review building plans to ensure they are consistent with the development package



If you have any questions about this transmittal, Contact Iman Monshizadeh at (520) 837-4082 or by email Iman.monshizadeh@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans
03/13/2020 RMCCOY1 BUILDING-COMMERCIAL REVIEW Approved
03/23/2020 LOREN MAKUS ENGINEERING REVIEW Reqs Change 1. DP is required.
2. Show roof drainage and impact on pedestrian routes.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/18/2020 KROBLES1 OUT TO CUSTOMER Completed