Permit Number: T20CM01053
Parcel: 134170310

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM01053
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/21/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Remove the roof overhang located closer than 2 feet from the property line.

Replace the undersized garage beam or provide an engineer analysis with stamped plans.
02/02/2021 NMARTEL1 ZONING REVIEW Reqs Change PDSD TRANSMITTAL
Nicholas Martell, Planner
T20CM01053
Residential Addition/Pending Violation
February 02, 2021

The residential plans have been reviewed by the Zoning Review Section but cannot be approved until all zoning comments or concerns have been addressed.

1. The west side of the building is 8" from the property line. The allowable setbacks in the R-1 zone are 6' or 2/3 the height of the building, whichever is greater. A board of adjustment variance is the only application that can reduce the required setbacks under 1'. The applicant has the following options:
a. The applicant can demonstrate that the structures on the west side of the property are 1' or greater from the property line and apply for a Design Development Option (DDO).
b. The applicant can apply for a variance to reduce setbacks to 8".
c. The applicant can remove the structures that are in question.
The application information for a variance can be found at the following web address: https://www.tucsonaz.gov/files/pdsd/codes/Zoning_Administration_Application_BA_fillable.pdf
If the applicant decides to apply for the board of adjustment variance, the following is a transmittal for that application:

PROJECT: T20CM01053
7310 E Princeton Dr.

COMMENTS: The following comments are for the purpose of applying for a variance before the Board of Adjustment (UDC Section 3.10.1).

This site is located in the R-1 zone (UDC 4.7.9). Single-family residential is a permitted use in this zone (Table 4.8-2). See Use Specific Standards 4.9.7.B.6, .9 & .10.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A).

The applicant is proposing to reduce the side perimeter yard setbacks from 6'-4" to 8", based on a wall height of 9'-6", as measured from the WEST property line. A board of adjustment variance is required.

If you have any questions about this transmittal, please contact me at Nicholas.Martell@tucsonaz.gov