Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/19/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The plans note that two Broan L200 exhaust fans are required but only one is shown. Where is the other fan? [Second comment: Combining mechanical ventilation and natural ventilation is not prohibited but at least one of the methods must be in full compliance. Mechanical exhaust, however, is required. Reference: footnote (b), Table 403.3.1.1 and Section 403.2.1 (3), IMC 2018.] [Initial comment: Revise the ventilation rates for the people, the room area in the beauty salon, and the required exhaust per Table 403.3.1.1, IMC 2018 (20 CFM per person, 0.12 CFM/SF, and 0.6 CFM/SF).] |
11/19/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Comment not addressed. [Second comment: Comment not addressed.] [Initial comment: Provide the third-party listing information for the specified shampoo sinks. Reference: Section 303.4, IPC 2018.] |