Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM01035
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/26/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Comment not addressed. [Initial comment: Provide the third-party listing information for the specified shampoo sinks. Reference: Section 303.4, IPC 2018.] |
| 03/26/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Combining mechanical ventilation and natural ventilation is not prohibited but at least one of the methods must be in full compliance. Mechanical exhaust, however, is required. Reference: footnote (b), Table 403.3.1.1 and Section 403.2.1 (3), IMC 2018. [Initial comment: Revise the ventilation rates for the people, the room area in the beauty salon, and the required exhaust per Table 403.3.1.1, IMC 2018 (20 CFM per person, 0.12 CFM/SF, and 0.6 CFM/SF).] |
| 04/03/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 04/15/2020 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 04/20/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/17/2020 | SROGERS2 | REJECT SHELF | Completed |