Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T20CM01025
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/18/2020 | IMONSHI1 | ZONING | REVIEW | Approved | |
| 02/18/2020 | IMONSHI1 | ENGINEERING | REVIEW | Passed | |
| 02/19/2020 | TWEIDEM1 | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | SHT. A-1 CALLS OUT INCORRECT BUILDING CODES. THE COT HAS ADOPTED THE 2018 BUILDING CODES AND THE 2017 NEC. PLEASE MAKE SHEET CORRECTIONS. THE COT USED A 115 MPH WIND SPEED, NOT 104 MPH AS SHOWN UNDER ROOF LOADS ON SHT. A-1. REMOVE REFERENCE SHT. A-7 FROM THE PLANS AND MAKE IT ITS OWN REFERENCE FILE. INCLUDE RACKING SHEETS IN THE REFERENCES. PLEASE QC ALL PLAN AND REFERENCE SHEETS FOR CORRECT INFORMATION PRIOR TO RESUBMITTAL. TOM WEIDEMAN 520-837-6823 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/19/2020 | TWEIDEM1 | APPROVAL SHELF | Completed |
| 02/19/2020 | TWEIDEM1 | OUT TO CUSTOMER | Completed |
| 02/19/2020 | TWEIDEM1 | REJECT SHELF | Completed |