Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T20CM01024
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/13/2020 | IMONSHI1 | ZONING | REVIEW | Reqs Change | FROM: Iman Monshizadeh PDSD Zoning Review Section PROJECT: T20CM01024 - Residential PV Building Plan Review (1st Review) 3927 E HARDY RD / R-2 Zoning TRANSMITTAL DATE: February 13th, 2020 COMMENT: The structure has an unpermitted addition to the north east of the property. The proposed PV is going to be placed on top of the addition. Provide permits for the addition or remove solar panels placed on addition on the next submittal If you have any questions about this transmittal, Contact Iman Monshizadeh at (520) 837-4082 or by email Iman.Monshizadeh@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov |
| 03/04/2020 | TWEIDEM1 | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | SHT. A-1. UPDATE THE ADDRESS. SHTS. A-2 AND A-3. SEE ZONING COMMENTS. SHTS. A-5 AND A-6. MAIN PANEL BKRS. DO NOT COMPLY WITH THE 120% RULE. WIRING APPEARS TO BE UNDERSIZED ALSO. DELETE SHT A-7 FROM THE PLAN SET. PROVIDE A SEPARATE FILE FOR THE REFERENCES, IE, SOLAR PANELS, INVERTER(S), RACKING. RENAME THE RESUBMITTED FILES 2_PLANS AND 2_REFERENCES. RE-NUMBER ALL PLAN SHTS. TOM WEIDEMAN 520-837-6823 |
| 03/04/2020 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/04/2020 | TWEIDEM1 | APPROVAL SHELF | Completed |
| 03/04/2020 | TWEIDEM1 | OUT TO CUSTOMER | Completed |
| 03/04/2020 | TWEIDEM1 | REJECT SHELF | Completed |