Review Date Reviewer's Name Type of Review Description Status Comments
02/12/2020 NMARTEL1 ZONING REVIEW Approved
02/12/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Does the existing supply or return ductwork penetrate the new fire-rated partition.
02/12/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
02/12/2020 NMARTEL1 ENGINEERING REVIEW Passed
02/12/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G2; Area of Work: The Area of Work includes a rated wall around this area (see Sheet A1). The 70 occupants require 2 exits. One of these exits must go through part of the building not included in this permit. Are these corridors rated? Please verify.
2. Sheet A1; Floor Plan: New doors 100, 101, and 103 must swing in the direction of egress per the IBC Section 1010.1.2.1. Please revise.
3. Sheet A2; Ceiling Plan: This plan indicates a single exit sign in the Area of Work. Please indicate additional signs as required. Are there directional exit signs in the existing part of the building not included in this permit? Please verify.
4. Sheet A3; Detail 1: Please indicate a U.L. Listing Number for this rated wall assembly.
5. General: Please provide written responses to all review comments.
02/12/2020 ROBERT SHERRY WATER REVIEW Completed
02/12/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
02/12/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/20/2020 JWILLIA2 FIRE REVIEW Reqs Change

Final Status

Task End Date Reviewer's Name Type of Review Description
02/20/2020 JWILLIA2 OUT TO CUSTOMER Completed