Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM01006
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/12/2020 | NMARTEL1 | ZONING | REVIEW | Approved | |
| 02/12/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Does the existing supply or return ductwork penetrate the new fire-rated partition. |
| 02/12/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 02/12/2020 | NMARTEL1 | ENGINEERING | REVIEW | Passed | |
| 02/12/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet G2; Area of Work: The Area of Work includes a rated wall around this area (see Sheet A1). The 70 occupants require 2 exits. One of these exits must go through part of the building not included in this permit. Are these corridors rated? Please verify. 2. Sheet A1; Floor Plan: New doors 100, 101, and 103 must swing in the direction of egress per the IBC Section 1010.1.2.1. Please revise. 3. Sheet A2; Ceiling Plan: This plan indicates a single exit sign in the Area of Work. Please indicate additional signs as required. Are there directional exit signs in the existing part of the building not included in this permit? Please verify. 4. Sheet A3; Detail 1: Please indicate a U.L. Listing Number for this rated wall assembly. 5. General: Please provide written responses to all review comments. |
| 02/12/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 02/12/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 02/12/2020 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 02/20/2020 | JWILLIA2 | FIRE | REVIEW | Reqs Change |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/20/2020 | JWILLIA2 | OUT TO CUSTOMER | Completed |