Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T20CM01000
Parcel: 12809005G

Address:
5353 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM01000
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/12/2020 NMARTEL1 ZONING REVIEW Approved
02/12/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
02/12/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Passed