Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T20CM00988
Parcel: 12801001B

Address:
170 S WILMOT RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T20CM00988
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/25/2020 MARTIN BROWN FIRE REVIEW Approved
03/04/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide a grounding detail for the racking and module grounding that shows compliance with NEC art 690.40.
2. Provide a detail showing the inverter and associated equipment mounting. If pole mounted, include distances above grade. If the inverter is mounted at a not readily accessible location, provide compliance with NEC 705.70.
3. Verify that the bus in the service equipment at the exact point of interconnection is factory marked "TAP". If not, provide a letter or document from the manufacturer of the service equipment stating that the line side tap as proposed will in no way compromise the listing or the performance of the equipment, signed by a person that has the authority by that manufacturer to make such a statement. Include all hardware used with a detail. Otherwise, provide for a field evaluation by an NRTL or qualified agency to be performed after the proposed tap is complete to re-certify and maintain the listing of the equipment. NEC 110.3, 230.66.
Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal requirements.
03/04/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/05/2020 IMONSHI1 ZONING REVIEW Approved
03/09/2020 PMARTIN1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/09/2020 PMARTIN1 OUT TO CUSTOMER Completed